ESS30-S002-DC24V-8A - ETA Electronic circuit breaker
Electronic circuit breaker with current limiter
Manual on/off switch (pressure/pressure actuation)
Operating voltage DC 24 V
Rated current 8A
- Buy 10 for €79.08 each and save 5%
- Buy 25 for €72.59 each and save 12%
- Buy 50 for €66.76 each and save 20%
- Buy 100 for €64.81 each and save 22%
Artikel dem Warenkorb hinzufügen oder Alles auswählen
The ESS30-S electronic circuit breaker with galvanic isolation is a "Low Energy Breaker", the world's only electronic overcurrent protection for DC 24 V applications. For use in decentralised and central power supply units, it meets the requirements of DIN EN 60934, UL 1077 as a supplementary protector and UL 1310 as a "Class 2 power unit" (NEC class2). The compact device is designed for pluggable mounting on the 17plus and 18plus base systems and the SVS power distribution systems and guarantees quick and easy installation.
The ESS30-S is just 12.5 mm wide and selectively protects all DC 24 V load circuits. This is achieved by a combination of active electronic current limitation in the event of a short circuit and an overload cut-out at typ. 1.2 x IN. DC 24 V switched-mode power supply units are used very frequently in automation technology. In the event of an overload, however, they regulate the output voltage that is to supply all connected loads. If a fault occurs in a single load in the system, the voltage also drops in all other load circuits. This often results not only in an undefined fault condition, but also in the machine or system coming to a standstill.
The maximum possible overcurrent is always limited to 1.2 times the selected rated current (see Table 1). This makes it easy to switch on capacitive loads up to 40,000 μF. The rated current is available in fixed values of 0.5 A...10 A and in the adjustable variants 1 A/2 A or 3 A/6 A.
Operating and error states are indicated by a multi-coloured LED and integrated signal outputs. The manual ON/OFF switch directly on the device allows targeted commissioning of individual load circuits and resetting after overcurrent-related switch-offs.
Key features:
-
Pluggable on power distribution modules 17plus, 18plus and SVSxx
-
Galvanic isolation in the event of a fault
-
Active linear current limitation
-
Capacitive loads up to 40,000 μF
-
Fixed rated currents 0.5 A...10 A (0.5A...3.6A NEC Class 2)
-
2 stages (1 A/2 A or 3 A/6 A) adjustable via switch on the device
-
Approvals: UL, NEC Class 2, VDE
-
Reduces storage costs as one device covers 2 rated currents
-
Offers high flexibility thanks to pluggability and simple adjustment of the rated currents
-
Saves costs, as the devices up to 3.6A with UL1310 (NEC Class 2) approval replace the expensive switching power supplies intended for this purpose
-
Saves energy costs thanks to 1/3 lower power loss than comparable solutions
-
Increases system availability thanks to clear fault detection and signalling
Technical data:
| operating data | |
| operating voltage UB | dC 24 V (18...30 V) |
| rated current IN | fixed currents: type ESS30-S 0.5 A; 1 A; 2 A; 2 A CL2; 3 A; 3 A CL2; 3.6 A; 3.6 A CL2; 4 A; 6 A; 8 A; 10 A; adjustable: 1 A/2 A or 3 A/6 A |
| quiescent current I0 | in the ON state: typ. 4 mA with the adjustable typ. 5.5 mA |
| tripping current (bimetal) | typ. 0.4 A (only in the event of a fault, until galvanic switch-off) |
|
signalling of the operating status via |
|
| load circuit | |
| load output | power - MOSFET switching output (positive switching) |
Overload cut-off (ÜL) and Short-circuit current cut-off |
typ. 1.2 x IN with active current limitation |
|
switch-off times for electron. Switch-off for galvanic isolation |
see time / current characteristic curve Overload switch-off time typ. 500 ms short-circuit switch-off time depending on rated current (see Table 1) typ. 5 s (3...9 s) |
| temperature switch-off |
Internal temperature monitoring with galvanic isolation |
|
undervoltage monitoring |
with hysteresis, no reset necessary: |
| switch-on delay tStart | typ. 2 ms after each switch-on and after the application of UB |
| capacitive loads | up to 40,000μF |
| freewheeling circuit | external freewheeling diode recommended for inductive loads |
| parallel connection of several load outputs | not permitted |
| error message, signal output | |
| error message F | potential-free signal contact , switches simultaneously with galvanic isolation max. DC 30 V/ 2 A, min. 12 V/10 mA |
| signal output ESS30-S001 Signal contact changeover contact |
blue push-button is in the on position: Signal contact 13/14-12 closed Blue push-button is in the off position: Signal contact 13/14-12 open |
| signal output ESS30-S002 Signal contact changeover contact |
blue push-button is in the On position: Signal contact 13/14-12 open Blue push-button is in the Off position: Signal contact 13/14-12 closed |
Signal output ESS30-S003 Signal contact changeover contact |
blue push-button is in the on position: Signal contact 13-14 is closed, 13-12 is open Blue push-button is in the off position: Signal contact 13-14 is open, 13-12 is closed |
| visual display | lED green UB is on and switch S1 is ON and no overload, no short circuit lED off
lED orange Overload condition > 1.2 x IN up to |
| general data | |
| fail-safe element |
back-up fuse for ESS30-S.. not necessary, as a redundant |
| flat plug connections | 6.3 mm in accordance with EN 60934-6.3-0.8 |
| housing material | plastic |
| housing fastening | pluggable in bayable power distributor Module 17plus or 18plus from E-T-A |
| ambient temperature | 0...+60 °C (without condensation, see EN 60204-1) |
| storage temperature | -40...+70 °C |
| humidity Heat | 96 hours/95 % relat. Humidity/40 °C according to IEC 60068-2-78, Test Cab. Climate class 3K3 according to EN 60721 |
| vibration resistance | 3 g, test according to IEC 60068-2-6, test Fc |
| protection class |
actuation range IP30 EN 60529 |
| eMC requirements (EMC Directive, CE marking) |
interference emission: EN 61000-6-3 Interference immunity: EN 61000-6-2 |
| insulation coordination (IEC 60934) |
0.5 kV/pollution degree 2 Reinforced insulation in the actuation area |
| insulation voltage | dC 500 V Between the galvanically isolated areas: load circuit in off-state, signal input and signal outputs |
|
dielectric strength |
(see also dimensional drawing) Test voltage AC 1 000 V Test voltage AC 500 V Test voltage AC 500 V |
|
approvals |
cE mark |
| insulation resistance (off state) |
> 100 MΩ (DC 500 V) between LINE (+) - LOAD (+) |
| installation dimensions (W x H x D) | see dimensional drawing 12.5 x 105 x 60 mm |
|
actuating forces |
5...8 N |
| weight | approx. 39 g |
Approvals:
| test centre | Test standard | rated voltage | rated current range |
File- |
| uL | uL 2367 | dC 32 V | 0,5...10 A | e306740 |
| uL |
uL 1310 |
dC 28 V |
0.5 A, 1 A, 2 A, |
e306740 |
| uL | uL 2367 | dC 24 V | 0.5 A...10 A | e306740 |
| uL |
uL 1077 |
dC 24 V |
0.5 A...10 A, |
e67320 |
| vDE |
iEC/EN |
dC 24 V | 5 A...10 A | 40039681 |
Table 1: Voltage drop, current limitation, max. load current
|
Rated current |
typ. Voltage drop |
active current |
Switch-off |
Switch-off Time |
Fail-safe |
max. load current |
||
|
tU = 40 °C |
tU = 50 °C |
tU = 60 °C |
||||||
|
0,5 A |
90 m V |
1.2 x IN |
500 ms |
500 ms |
2 A |
0,5 A |
0,5 A |
0,5 A |
|
1 A |
100 mV |
1.2 x IN |
500 ms |
500 ms |
2 A |
1 A |
1 A |
1 A |
|
2 A |
110 m V |
1.2 x IN |
500 ms |
500 ms |
4 A |
2 A |
2 A |
2 A |
|
2 A CL2 |
130 mV |
1.2 x IN |
500 ms |
500 ms |
4 A |
2 A |
2 A |
2 A |
|
3 A |
150 m V |
1.2 x IN |
500 ms |
500 ms |
6,3 A |
3 A |
3 A |
3 A |
|
3 A CL2 |
200 mV |
1.2 x IN |
500 ms |
500 ms |
4 A |
§ A |
3 A |
3 A |
|
3,6 A |
155 mV |
1.2 x IN |
350 ms |
500 ms |
6,3 A |
3,6 A |
3,6 A |
3,6 A |
|
3.6 A CL2 |
220 mV |
1.05 x IN |
450 ms |
500 ms |
4 A |
3,6 A |
3,6 A |
3,6 A |
|
4 A |
160 m V |
1.2 x IN |
280 ms |
500 ms |
6,3 A |
4 A |
4 A |
4 A |
|
6 A |
170 m V |
1.2 x IN |
150 ms |
500 ms |
10 A |
6 A |
6 A |
6 A |
|
8 A |
190 mV |
1.2 x IN |
280 ms |
500 ms |
15 A |
8 A |
7,5 A |
7 A |
|
10 A |
210 mV |
1.2 x IN |
200 ms |
500 ms |
15 A |
9,5 A |
9 A |
8,5 A |
|
1 A/2 A |
140 mV/90 mV |
1.2 x IN |
500 ms |
500 ms |
4 A |
1 A/2 A |
1 A/2 A |
1 A/2 A |
|
3 A/6 A |
80 mV/160 mV |
1.2 x IN |
500 ms/150 ms |
500 ms |
10 A |
3 A/6 A |
3 A/6 A |
3 A/6 A |
| Item name | ESS30-S002-DC24V-8A - ETA Electronic circuit breaker |
|---|---|
| SKU | 24-01780 |
| Weight | 0.048200 |
| Country of manufacture | Germany |
| Connection type Main connections | P10 flat plug DIN 46244-A6.3-0.8 |
| Signal output | 2 Signal contact NC contact |
| Design: Communication, interface | 0 ohne Steuereingang |
| Series | ESS30 |
| Version | 0 mit galvanischer Trennung im Fehlerfall |
| Manufacturer | E-T-A |
| Manufacturer number | 0ESS30003160 |
| Additional function | 0 ohne |
| Actuating element | W Standard rocker switch |
| Undervoltage module | none |
| Operating voltage | DC 24 V Nennspannung DC 24 V |
| Number of poles | 1-pole thermally protected |
| Rated current range | 8A |
| Mounting type | S Pluggable |
| Characteristic | Medium time-lag tripping characteristic (standard) |
| Commodity code | 85362010 |
| Traub order number | ESS30-S002-DC24V-8A |
E-T-A
Elektrotechnische Apparate GmbH
Industriestraße 2-8
90518 Altdorf b. Nürnberg
Deutschland
order@e-t-a.de