8340-F420-P1M1-ALH0-6A ETA Hydraulic magnetic circuit breaker

E-T-A Hydraulic magnetic circuit breaker
2-pole protected, hydraulic magnetic delayed
Without auxiliary contacts
Rated current range 6 A

€193.08
  • Buy 10 for €161.85 each and save 16%
  • Buy 100 for €93.65 each and save 51%
Incl. 19% Tax, plus Shipping
Delivery within 57 to 59 days within Germany, reordering within 56 days.
Not in stock, will be ordered for you.
SKU
24-01567
8340-F420-P1M1-ALH0-6A ETA Hydraulic magnetic circuit breaker is available to buy in increments of 1

Single and multi-pole circuit breaker with magnetic or hydraulic-magnetic tripping, toggle lever actuation, front mounting, various characteristic curves and optional auxiliary contacts. A precise switching mechanism ensures unaffected free tripping and reliable disconnection even with the smallest overcurrents. Low temperature sensitivity at nominal load. Complies with the appliance circuit breaker standard EN 60934 (IEC 60934): S-type, HM or MO.

Typical areas of application
Power supplies, switchgear, control and regulation technology, telecommunications, fixed and mobile networks

Technical data

rated voltage

3 AC 415 V; AC 240 V (50/60 Hz); DC 80 V
(higher DC voltages on request)

nominal current range 0.02...50 A DC
0.02...30 A AC
auxiliary circuit aC 240 V 6 A DC 28 V 3 A
DC 65 V 1 A DC 80 V 0.5 A
lifetime 3 AC 415 V, AC 240 V:
0.02...30 A 6,000 switching cycles with 1 x IN, inductive
10,000 switching cycles with 1 x IN, ind.arm

DC 80 V:
0.02...25 A 6,000 switching cycles with 1 x IN, inductive

0.02...30 A 10 000 switching cycles with 1 x IN, ind.arm
40 + 50 A 6 000 switching cycles with 1 x IN, ind.arm

ambient temperature -40 °C...85 °C

insulation coordination
(IEC 60664)

2.5 kV/2
(IEC 60664) Reinforced insulation in the actuating range
dielectric strength
Actuation range
Line to load
Pole to pole (2- and 3-pole) Main 3-pole)
Main to auxiliary circuit
Switching to tripping circuit
(version X)
test voltage AC 3 000 V
Test voltage AC 1 500 V
Test voltage AC 1 500 V
Test voltage AC 3 000 V
Test voltage AC 1 500 V
insulation resistance > 100 MΩ (DC 500 V)
switching capacity 6 x IN with AC;
IEC 60934 - Test series E
6 x IN for AC;
4 x IN for DC
switching capacity (UL 1077) aC:
1-pole AC 240 V/3 500 A AC 240 V/3 500 A
2-pole AC 240 V/3 500 A AC2 40 V/5 000 A
3-pole 3 AC 240 V/3 500 A 3 AC 240 V/5 000 A

dC:
1-pole 0.02...50 A DC 80 V/3 500 A
2-pole 0.02...30 A DC 80 V/3 500 A

protection class (IEC 60529) actuation range IP40
Connection range IP00
vibration resistance (UL 1077) 0.02...20 A 25...30 A
AC:
1-pole AC 240 V/3 500 A AC 240 V/3 500 A
2-pole AC 240 V/3 500 A AC2 40 V/5 000 A
3-pole 3 AC 240 V/3 500 A 3 AC 240 V/5 000 A DC:
1-pole 0.02...50 A DC 80 V/3 500 A
2-pole 0.02...30 A DC 80 V/3 500 A
vibration resistance


For characteristic curves F1, F2:
installation position rocker arm downwards: at 0.9 x IN
10 g (57-2000 Hz) ± 0.76 mm (10-57 Hz)

Other installation positions:
10 g (57-2000 Hz) at IN
all mounting positions at 0.8 x IN
10 g (57-2000 Hz) ± 0.76 mm (10-57 Hz)
Test in accordance with IEC 60068-2-6, test Fc,
10 frequency cycles/axis
shock resistance
Shock direction 1, 2, 3, 4, 5:
Shock direction 6:
Characteristic curves F1, F2:
100 g (11 ms) at IN
100 g (11 ms) at 0.8 x IN
100 g (11 ms) at 0.8 x IN
Test in accordance with IEC 60068-2-27, Test Ea
corrosion resistance 96 hours in 5 % salt spray,
Test in accordance with IEC 60068-2-11, test Ka
moisture test 240 hours in 95 % relative humidity,
Test in accordance with IEC 60068-2-78, Test Cab
mass approx. 65 g per pole


Approvals

test centre test standard rated voltage rated current range
vDE

iEC / EN
60934

aC 240/415 V
AC 240 V
DC 80 V
0.02 A...30 A
0.02 A...30 A
0.02 A...50 A
uL uL 1077 aC 250 V
DC 80 V
DC 80 V
0.02 A...30 A
0.02 A...50 A
100 A (2 poles in parallel)
uL uL 489A dC 80 V 0.05 A...30 A
(1 + 2 poles)
cSA c22.2 No
235
aC 250 V
DC 80 V
0.02 A...30 A
0.02 A...30 A
cQC gB 17701 aC 240/415 V
AC 240 V
DC 80 V
0.02 A...30 A
0.02 A...30 A
0.02 A...50 A
qPL
Sweden
Defence
Material
Admin.
mIL-C-
55629
aC 240 V
DC 50 V
AC 240 V
AC 240 / 415 V
1 A...30 A (8340-F410)
1 A...30 A (8340-410)
1 A...30 A (8340-F420)
1 A...30 A (8340-F430)
More Information
Item name 8340-F420-P1M1-ALH0-6A ETA Hydraulic magnetic circuit breaker
SKU 24-01567
Weight 0.128000
Output drive P1 Flat plug DIN 46244-A6,3x0,8
Labelling on actuating element L I-O; ON-OFF
Colour and type of actuating element A black
Auxiliary contact terminal form 2 Flachstecker DIN 46244-A2,8-0,5
Auxiliary contact function 4 1 Wechsler
Auxiliary contact variants H0 without auxiliary contacts
Average tripping characteristic hydraulically delayed M1 DC
Dimension and shape 4 with M3 fixing nuts
Country of manufacture Germany
Accessories 0 without accessories
Rated current 6 A
Traub order number 8340-F420-P1M1-ALH0-6A
Commodity code 85362010
Manufacturer E-T-A
Manufacturer number 8340-F420-P1M1-ALH0-6A
Number of poles 1-pole thermally protected
Mounting type F Flange mounting
Series 8340

E-T-A
Elektrotechnische Apparate GmbH
Industriestraße 2-8
Altdorf b. Nürnberg
Deutschland
order@e-t-a.de
e-t-a.de