2215-G111-P1T1-S11-6A ETA Thermal magnetic circuit breaker
Thermal magnetic circuit breaker
1-pole protected
Rated voltage 6 A
- Buy 10 for €61.38 each and save 16%
- Buy 100 for €35.52 each and save 51%
Single-pole, thermal-magnetic circuit breakers in small design with toggle lever actuation, threaded neck or printed circuit board mounting, uninfluenced free tripping, various characteristic curves and optional auxiliary contacts.can also be used in power distribution systems - see product group Power distribution systems - Customised solutions. Complies with the EN 60934 (IEC 60934) miniature circuit-breaker standard: S-type, TM.
Typical areas of application
Power supplies, control and regulation technology, protection of electronic assemblies (suitable for mounting on Eurocards)
| rated voltage | aC 250 V (50/60 Hz); DC 50 V (higher DC voltages on request) |
| nominal current range | 0,05...10 A |
| auxiliary circuit | aC 250 V / DC 28 V, 1 A |
| service life | 10,000 switching cycles with 1 x IN |
| ambient temperature | -30...60 °C |
| insulation coordination (IEC 60664) | 2.5 kV/2 reinforced insulation in the actuating range |
| dielectric strength actuating range Main to auxiliary circuit |
test voltage AC 3 000 Test voltage AC 1 500 V |
| open auxiliary circuit AC 1000 V | aC 1000 V |
| insulation resistance | > 100 MΩ (DC 500 V) |
| switching capacity Icn | 300 A |
| switching capacity (UL 1077) | iN UN
0.05 A AC 250 V 200 A |
| protection class (IEC 60529) | actuation range IP30 Connection range IP00 |
| vibration resistance Characteristic curve F1: Characteristic curves F2, M1 |
8 g (57-500 Hz) ± 0.61 mm (10-57 Hz) |
| shock resistance Characteristic curves F1, M1, T1: Characteristic curves F1: Characteristic curves M1, T1: |
30 g (11 ms) for impact direction 1, 2, 3, 4, 5 10 g (11 ms) for impact direction 6 15 g (11 ms) for impact direction 6 Test in accordance with IEC60068-2-27, Test Ea |
| corrosion resistance | 96 hours in 5 % salt spray, Test in accordance with IEC 60068-2-11, test Ka |
| moisture test | 240 hours in 95 % relative humidity, Test in accordance with IEC 60068-2-78, Test Cab |
| mass | approx. 25 g |
Approvals
| test centre | standard | rated voltage | rated current range |
| uL | uL 1077 | aC 250 V DC 75 V |
0.05 A...10 A 0.05 A...10 A (20 A) |
| cSA |
c22.2 |
aC 250 V |
0.05 A...10 A |
| Item name | 2215-G111-P1T1-S11-6A ETA Thermal magnetic circuit breaker |
|---|---|
| SKU | 24-00905 |
| Weight | 0.031300 |
| Characteristic | T1 inert: therm. 1.01-1.4 x IN; magn. 8-17 x IN DC; magn. 6-13 x IN AC |
| Country of manufacture | Indonesia |
| Signal contact connections | 0 without |
| Series | 2215 |
| Mounting type | G1 threaded fastening with screwed-on hexagon and plastic knurled nut |
| Number of poles | 1-pole |
| Auxiliary contact | S11 with auxiliary contact (change-over contact) blade terminal DIN 46244-A6,3-0,8 |
| Rated current range | 6A |
| Auxiliary contact Terminal form | 1 wie Hauptkontaktanschlüsse |
| Additional function/accessories | ohne |
| Traub order number | 2215-G111-P1T1-S11-6A |
| Commodity code | 85362010 |
| Manufacturer | E-T-A |
| Manufacturer number | 221500006156C |
| Actuating element | W Standard rocker switch |
E-T-A
Elektrotechnische Apparate GmbH
Industriestraße 2-8
90518 Altdorf b. Nürnberg
Deutschland
order@e-t-a.de
e-t-a.de