2215-G111-P1M1-S0-3A ETA Thermal magnetic circuit breaker

Thermal magnetic circuit breaker
1-pole protected
Rated voltage 3 A

€67.26
  • Buy 10 for €56.38 each and save 16%
  • Buy 100 for €32.63 each and save 51%
Incl. 19% Tax, plus Shipping
Delivery within 29 to 31 days within Germany, reordering within 28 days.
2215-G111-P1M1-S0-3A ETA Thermal magnetic circuit breaker has a minimum order quantity of 10 pieces
Not in stock, will be ordered for you.
SKU
24-01655
2215-G111-P1M1-S0-3A ETA Thermal magnetic circuit breaker is available to buy in increments of 1

Single-pole, thermal-magnetic circuit breakers in small design with toggle lever actuation, threaded neck or printed circuit board mounting, uninfluenced free tripping, various characteristic curves and optional auxiliary contacts.can also be used in power distribution systems - see product group Power distribution systems - Customised solutions. Complies with the EN 60934 (IEC 60934) miniature circuit-breaker standard: S-type, TM.

Typical areas of application
Power supplies, control and regulation technology, protection of electronic assemblies (suitable for mounting on Eurocards)

rated voltage aC 250 V (50/60 Hz); DC 50 V
(higher DC voltages on request)
nominal current range 0,05...10 A
auxiliary circuit aC 250 V / DC 28 V, 1 A
service life 10,000 switching cycles with 1 x IN
ambient temperature -30...60 °C
insulation coordination (IEC 60664) 2.5 kV/2 reinforced insulation in the actuating range
dielectric strength actuating range
Main to auxiliary circuit
test voltage AC 3 000
Test voltage AC 1 500 V
open auxiliary circuit AC 1000 V aC 1000 V
insulation resistance > 100 MΩ (DC 500 V)
switching capacity Icn 300 A
switching capacity (UL 1077) iN UN

0.05 A AC 250 V 200 A
0.1...6 A AC 250 V 1 000 A
8...10 A AC 250 V 2 000 A
0.05...10 A DC 50 V 1 000 A

protection class (IEC 60529) actuation range IP30
Connection range IP00
vibration resistance
Characteristic curve F1:

Characteristic curves F2, M1


6 g (57-500 Hz), ± 0.46 mm (10-57 Hz);

8 g (57-500 Hz) ± 0.61 mm (10-57 Hz)
Test according to IEC 60068-2-6, test Fc,
10 frequency cycles/axis

shock resistance
Characteristic curves F1, M1, T1:
Characteristic curves F1:
Characteristic curves M1, T1:

30 g (11 ms) for impact direction 1, 2, 3, 4, 5
10 g (11 ms) for impact direction 6
15 g (11 ms) for impact direction 6
Test in accordance with IEC60068-2-27, Test Ea
corrosion resistance 96 hours in 5 % salt spray,
Test in accordance with IEC 60068-2-11, test Ka
moisture test 240 hours in 95 % relative humidity,
Test in accordance with IEC 60068-2-78, Test Cab
mass approx. 25 g


Approvals

test centre standard rated voltage rated current range
uL uL 1077 aC 250 V
DC 75 V

0.05 A...10 A
0.05 A...10 A (20 A)
cSA

c22.2
No. 235

aC 250 V
DC 75 V

0.05 A...10 A
0.05 A...10 A (20 A)

More Information
Item name 2215-G111-P1M1-S0-3A ETA Thermal magnetic circuit breaker
SKU 24-01655
Weight 0.030600
Characteristic M1 Thermal 1.15 - 1.4 x IN
Country of manufacture Indonesia
Signal contacts S0 without signal contacts
Signal contact connections 0 without
Series 2215
Mounting type G1 threaded fastening with screwed-on hexagon and plastic knurled nut
Number of poles 1-pole
Rated current range 3A
Auxiliary contact Terminal form 1 wie Hauptkontaktanschlüsse
Additional function/accessories 0 ohne
Traub order number 2215-G111-P1M1-S0-3A
Commodity code 85362010
Manufacturer E-T-A
Manufacturer number 2215-G111-P1M1-S0-3A
Actuating element W Standard rocker switch

E-T-A
Elektrotechnische Apparate GmbH
Industriestraße 2-8
90518 Altdorf b. Nürnberg
Deutschland
order@e-t-a.de
e-t-a.de