2210-T210-K0M3-H121-2A ETA Thermal magnetic circuit breaker
E-T-A Thermal magnetic circuit breaker
1-pole protected
Terminal connections
Rated current: 2 A
- Buy 10 for €74.59 each and save 16%
- Buy 100 for €43.16 each and save 51%
Artikel dem Warenkorb hinzufügen oder Alles auswählen
Single and multi-pole, thermal-magnetic circuit-breakers with toggle lever actuation, unaffected free tripping, various characteristic curves, all-pole tripping, for DIN rail mounting. Optionally with auxiliary contact.
Complies with the EN 60934 (IEC 60934) appliance circuit breaker standard: S-type, TM.
Typical areas of application:
Telecommunications, power supplies, industrial switching and control systems, railway technology, infrastructure, marine, construction machinery
| rated voltage |
aC 250 V; 3 AC 433 V (50/60 Hz); DC 65 V |
| nominal current range |
0.1...32 A for characteristic curves M1, T1 |
| auxiliary circuit | aC 240 V / DC 65 V 1 A, low-inductance (min. 10 V / 10 mA) |
| ambient temperature | -30...60 °C (T 60) |
| insulation coordination (IEC 60664) | 2.5 kV/2 reinforced insulation in the actuation area |
| dielectric strength Actuating range Main to auxiliary circuit Pole to pole |
Test voltage AC 3 000 V Test voltage AC 3 000 V Test voltage AC 1 500 V |
| insulation resistance | > 100 MΩ (DC 500 V) |
| switching capacity Icn Characteristic curves F1,F2,M1,T1 |
0.1...5 A 400 A 6...32 A 800 A 0.1...16 A 2 500 A (at DC 32 V) |
| switching capacity (UL 1077) | iN 0.1...16 A 20...25 A
aC 277 V 1-pole 5 000 A 2 000 A |
| protection class (IEC 60529) | actuation range IP30 Connection range IP20 |
| vibration resistance | characteristic F1, F2: 3 g (57-500 Hz), ± 0.23 mm (10-57 Hz); characteristic curves M1, M3, T1: |
| shock resistance | characteristic curves F1, F2:
25 g (11 ms) impact direction 1, 2, 3, 4, 5 characteristic curves M1, T1: 25 g (11 ms) impact direction 1, 2, 3, 4, 5 test according to IEC 60068-2-27, test Ea |
| corrosion resistance | 96 hours in 5 % salt spray, Test in accordance with IEC 60068-2-11, test Ka |
| moisture test | 240 hours in 95 % relative humidity, Test in accordance with IEC 60068-2-78, Test Cab |
| mass | approx. 60 g per pole |
| test point | rated voltage | rated current range |
| vDE (IEC/EN 60934) | 3 AC 433 V AC 250 V DC 65 V |
0,1...32 A |
| uL (UL 1077) | aC 277 V AC 277/480 V DC 65 V |
0,1...32 A |
| cSA (C22.2 No 235) |
aC 277 V AC 277/480 V DC 65 V |
0,1...32 A |
| cQC (GB 17701) | aC 250 V AC 250 V / 433 V DC 65 V |
0.1...25 A |
|
dNV GL (IEC 60934, DNVGLCG 0339) |
3 AC 250 V AC 250 V / 433 V DC 65 V |
0.1 A...32 A 0.1 A...32 A 0.1 A...32 A |
|
kTL (KC60934) |
aC 250 V, 1-pole |
|
| Item name | 2210-T210-K0M3-H121-2A ETA Thermal magnetic circuit breaker |
|---|---|
| SKU | 24-01643 |
| Weight | 0.060400 |
| Characteristic | M3 medium inertia, low resistance version: therm.1.4-1.8xIN; magn.6-12xIN AC;7.8-15.6xIN DC |
| Country of manufacture | Germany |
| Connection type Main connections | K0 Terminal connections |
| Series | 2210 |
| Mounting type | T Mounting rail fastening |
| Number of poles | 1-pole protected |
| Auxiliary contact | H without intermediate detent (standard) |
| Rated current range | 2A |
| Auxiliary contact Terminal form | 1 wie Hauptkontaktanschlüsse |
| Auxiliary contact variant | 1 with auxiliary contacts |
| Auxiliary contact function | 2 1 NO contact |
| Additional function/accessories | 0 ohne Zubehör |
| Traub order number | 2210-T210-K0M3-H121-2A |
| Commodity code | 85362010 |
| Manufacturer | E-T-A |
| Manufacturer number | 221000318135 |
| Actuating element | 2 Rocker arm |
E-T-A
Elektrotechnische Apparate GmbH
Industriestraße 2-8
90518 Altdorf b. Nürnberg
Deutschland
order@e-t-a.de